SINGLE-CHANNEL TYPE GAS DETECTOR RECEIVER GTC-540 SERIES |
| Model |
GTC-540 |
| Operation display |
6-LED(Power, 3-stage alarm, Trouble, Stand-by for maintenance) |
| Measuring display |
3-Digit 1.8” FND & Bar-Graph(32 Segment, 3-color LED) |
| Measuring range |
1~999 (programmable) / %LEL, ppm, %vol |
| Alarm display |
Visual : 3-stage alarm, Trouble LED, Warning Light |
| Audible : buzzer |
| Alarm output signal |
3-Stage Alarm, Trouble/ AC250V 3A relay contact (SPDT) |
| Shut-off Valve control signal (DC 12V) |
| Alarm level set |
Programmable with in detection range |
| Input signal |
4-20mA DC( 2-wire or 3-wire) |
| Output signal |
4-20mA DC |
| Isolated RS-485 Communication Modbus (option) |
| Reset signal |
Reset switch and remote control |
| Program set mode |
Alarm value (1,2,3 alarm) |
| Alarm time (instant & delay) 1~30min |
| Alarm dead band |
| Measuring value offset (SAD) |
| Relay output on/off |
| Operating temperature |
-20℃ ~ +50℃ |
| Operating humidity |
5~99% RH(non-condensing) |
| Operating power |
Standard : AC90V~250V / 12W max |
| 24V DC (Option) / 280mA max |
| Dimensions |
235.6x185x117.3 (WxHxD)mm |
| Weight |
1kg |